CFP 8 Zone Repeater Panel.

£134.77 ex. VAT - £161.72 inc. VAT

  • Up to 8 repeaters per CFP master.
  • Includes its own Mains power supply that requires its own standby battery supply.
  • Provides the user with access to all AL1 and AL2 functions.
  • Master/Repeater communication achieved using CFP761 network driver cards (one CFP761 is supplied with the Repeater, an additional CF761 card is required at the master CFP).
  • Communicates over screened two-wire fire resistant cable.
Contact Us Via WhatsApp

10 in stock (can be backordered)

Quantity:

Can be used to repeat the functions of a master CFP standard or AlarmSense 2-8 zone fire panel at remote parts of site (e.g. all potential fire service entrances).

Compatibility

  • Compatible with C-TEC’s CFP Standard and CFP AlarmSense panels. (CFP Economy panels cannot be extended with this product).
  • Mains supply: 230V 50/60Hz.
  • Internal power supply: 19V-28.5V (27V nominal).
  • Max battery size and type: 2 x 12V 2.1Ah VRLA connected in series for 72 hour standby. 2 x 12V 1.2Ah for 24 hours.
  • Max. network cable length: 1KM.
  • Product dimensions (mm): 380 W x 235 H x D 96mm.
  • Construction & finish: Plastic lid and base; RAL7035 textured
  • IP Rating: IP30.
  • Weight: 1.75kg (without batteries)
  • Operating conditions/temperature: 5ºC to +40ºC. Max relative humidity: 95%.

Datasheets